Cleaning:
-Terminal of the ACB which is plated has to be cleaned with cloth only.
Don’t use Steel brush for cleaning of breaker terminal.
Fig:Cleaning guide lines for breaker terminals
-Busbars before connection to be cleaned to obtain a bright finish with a steel wire brush.
Fig:Cleanig of busbars with steel brush
After removal of the metal particles with auto clean cloth, a thin film of neutral petroleum jelly to be applied immediately and connection made.
Fig:Petrolium jelly for busbar termination
.....