a) Step 1
Collect the system data for which busbar system has to be design
VOLTAGE RATING 415V, 50Hz. 3Ph. - 3Wire
CURRENT RATING 2000Amp.
WELL VENTILATED ROOM
MAX. FAULT CURRENT 50 KA
LENGTH OF BUSBAR = 500mm
AVERAGE AMBIENT TEMP. = 50 deg. Centigrade
Calculate the derating factors for ambient temperature, enclosure, proximity effect.
1) Derating factor for Ambient Temperature
Df1=0.81
Actual average ambient temp. = 50 deg. C
Manufacturer average ambient temp. = 35 deg. C
Final ambient temp. = 85 deg. C
2) Derating factor for enclosure & ventilation
From table we can see that for well ventilated room, where cross-sectional area of busbar is 10% of total cross-sectional area of enclosure derating factor is
Df2=0.65
3) Derating factor for Proximity effect
For 3W phase spacing derating factor for proximity effect is
Df3=0.82
Calculate effective derating factor.
Df = 0.81 * 0.65 * 0.82
= 0.43
Select the busbar size
Minimum rating of busbar required
= 2000/0.43
= 4651 amp.
Busbar selected = 203.2 * 9.53 mm (3 flats)